North American — FWP 700V: 5-1200A
North American style stud-mount fuses
————————————————————————————————
Description:
North American style stud-mount fuses.
Ratings:
Volts: 700Vac/dc
Amps: 5-1200A
IR: 200kA RMS Sym. 50kA @700Vdc
Agency Information: CE, UL Recognition & CSA Component Acceptance on 5-800A
Features and Benefits
• Excellent DC performance
• Low arc voltage and low energy let-through (I2t)
• Superior cycling capability
Typical Applications
• DC common bus
• DC drives
• Power converters/rectifiers
• Reduced voltage starters
Dimensions (in)
Order # | Fig. | A | B | C | D | E | F | G | H | J |
FWP-5B-30B | 1 | 2.87 | 0.563 | 1.855 | 2.477 | 2.477 | 0.25 | 0.405 | 0.063 | 0.25 |
FWP-35B-60B | 1 | 4.375 | 0.813 | 2.75 | 3.708 | 3.312 | 0.344 | 0.725 | 0.125 | 0.542 |
FWP-70B-100B | 1 | 4.406 | 0.947 | 2.594 | 3.625 | 3.563 | 0.344 | 0.75 | 0.125 | 0.375 |
FWP-125A-200A | 1 | 5.09 | 1.5 | 2.84 | 4.19 | 3.5 | 0.41 | 1 | 0.25 | 0.75 |
FWP-225A-400A | 1 | 5.09 | 2 | 2.84 | 4.28 | 3.53 | 0.41 | 1.5 | 0.25 | 0.78 |
FWP-450A-600A | 1 | 7.09 | 2.5 | 2.84 | 5.72 | 4.19 | 0.53 | 2 | 0.38 | 1.3 |
FWP-700A-800A | 1 | 6.63 | 2 | 2.844 | 5.562 | 5.062 | 0.625 | 1.5 | 0.25 | 0.875 |
FWP-900A-1000A | 2 | See Drawing | ||||||||
FWP-1200A | 3 |
Catalog Numbers
Electrical Characteristics | Ordering Information | Dimensions | ||||||
Type | Rated Current RMS-Amps | I2t (A2 Sec) | Watts Loss | Part Number | Carton Qty. | Carton Weight (lbs) | Figure Number | |
Pre-arc | Clearing at 700V | |||||||
FWP 700V | 5A | 1.6 | 10 | 1.5 | FWP-5B | 10 | 2.25 | Fig.1 |
10A | 3.6 | 20 | 4 | FWP-10B | ||||
15A | 10 | 75 | 5.5 | FWP-15B | ||||
20A | 26 | 180 | 6 | FWP-20B | ||||
25A | 44 | 340 | 7 | FWP-25B | ||||
30A | 58 | 450 | 9 | FWP-30B | ||||
35A | 34 | 160 | 12 | FWP-35B | 5 | 1.21 | ||
40A | 76 | 320 | 12 | FWP-40B | ||||
50A | 135 | 600 | 12 | FWP-50B | ||||
60A | 210 | 950 | 15.5 | FWP-60B | ||||
70A | 305 | 2000 | 18 | FWP-70B | 1 | 0.24 | ||
80A | 360 | 2400 | 21 | FWP-80B | ||||
90A | 415 | 2700 | 25 | FWP-90B | ||||
100A | 540 | 3500 | 27 | FWP-100B | ||||
125A | 1800 | 7300 | 28 | FWP-125A | 0.65 | |||
150A | 2900 | 11700 | 32 | FWP-150A | ||||
175A | 4200 | 16700 | 35 | FWP-175A | ||||
200A | 5500 | 22000 | 43 | FWP-200A | ||||
225A | 7700 | 31300 | 45 | FWP-225A | 1.17 | |||
250A | 10500 | 42500 | 48 | FWP-250A | ||||
300A | 17600 | 71200 | 58 | FWP-300A | ||||
350A | 23700 | 95600 | 65 | FWP-350A | ||||
400A | 31000 | 125000 | 78 | FWP-400A | ||||
450A | 36400 | 137000 | 94 | FWP-450A | 2.39 | |||
500A | 45200 | 170000 | 107 | FWP-500A | ||||
600A | 66700 | 250000 | 122 | FWP-600A | ||||
700A | 54000 | 300000 | 125 | FWP-700A | 1.21 | |||
800A | 78000 | 450000 | 140 | FWP-800A | ||||
900A | 91500 | 530000 | 150 | FWP-900A | 6.6 | Fig.2 | ||
1000A | 120000 | 600000 | 170 | FWP-1000A | ||||
1200A | 195000 | 1100000 | 190 | FWP-1200A | Fig.3 |
- 1 kg = 2.2 lbs 1 lb = 0.45 kg
- Interrupting rating 200kA RMS Symmetrical.
- Watts loss provided at rated current.
- (700 Vdc/Interrupting rating 50kA) U.L. Recognition & CSA Component Acceptance on 5 through 100 & 700 through 800 amperes.
- (700 Vdc/Interrupting rating 10kA) U.L. Recognition & CSA Component Acceptance on 125 through 600 amperes.