35kV cross-linking cable outdoor ,indoor terminal
双丰热缩的高压产品应用于35KV交联电缆的末端处理.
Shuangfeng shrink middle voltage products is suitable for the end dealing of the 35kV cross-linking cable .
产品规格型号 Product specification
产品名称 Name | 型号规格 Type | 适用电缆截面 Section |
35kV 户内交联单芯终端 35kV indoor cross-link single-cores terminal |
NSY-35/1.1 | 50-120 |
NSY-35/1.2 | 150-300 | |
NSY-35/1.3 | 400-500 | |
35kV 户外交联单芯终端 35kV outdoor cross-link single-cores terminal |
WSY-35/1.1 | 50-120 |
WSY-35/1.2 | 150-300 | |
WSY-35/1.3 | 400-500 | |
35KV 户内交联三芯终端 35kV indoor cross-link three-cores terminal |
NSY-35/3.1 | 50-120 |
NSY-35/3.2 | 150-300 | |
NSY-35/3.3 | 400-500 | |
35KV 户外交联三芯终端 35kV outdoor cross-link three-cores terminal |
WSY-35/3.1 | 50-120 |
WSY-35/3.2 | 150-300 | |
WSY-35/3.3 | 400-500 |
产品技术指标 Product technical index
项目Item | 试验顶目 Test item | 标准要求 Standard requirement | 试验结果 Result | 详注 Note | 备注 Note |
35kV户内,户外,终端 35kV outdoor indoor terminal |
1 工频耐压 | 105kV 不闪络,不击穿 | 105kV 1min 未闪络,未击穿 | 通过 pass |
武 高 所 试 验 |
2 局部放电试验 | 39kV≤10pC | 39KV≤10pC | 通过 pass |
||
3 负荷循环试验 3个周期 | 5h加热时,3h冷却, 加热时导体温度为95℃ |
同左 | 通过 pass |
||
4 局部放电试验 | 39kV≤10pC | 39KV 110pC | 通过 pass |
||
5 击冲电压试验1.2/ 50Us 正负极性各一次 |
250kV 正负极性各允许 闪络一次,但不计人总试验次数 |
250kV±次 未闪络,未击穿 | 通过 pass |
||
6 直流电压试验负极性 | 156kV 不闪络,不击穿 | 156kV/15min 未闪络,未击穿 | 通过 pass |
||
7 4h工频电压试验 | 104KV 4h 不闪络,不击穿 | 35KV/4h 未闪络,未击穿 | 通过 pass |
http://www.chsf.cc